Danfoss KVP Series

RC_PROD_006

/

Danfoss

/

Valves & Regulators

The Danfoss KVP is an evaporator pressure regulator that maintains constant minimum evaporating pressure in the suction line. Genuine Danfoss stock in Mumbai.

The Danfoss KVP is an evaporator pressure regulator installed in the suction line after the evaporator. It maintains a constant minimum evaporating pressure — and therefore a minimum evaporating temperature — regardless of falling suction pressure elsewhere in the system. This is essential in multi-evaporator installations where different evaporators must run at different temperatures on a common compressor, and in applications where product must be protected against freezing or dehumidification.

Rated and extended capacities for KVP valves are calculated with Danfoss's Coolselector®2 engine to ARI standards, giving procurement engineers reliable selection data.

Sizes available — the number is the line size, not the capacity: KVP 12 (½ in / 12 mm, flare or solder), KVP 15 (⅝ in / 16 mm, flare or solder), KVP 22 (⅞ in / 22 mm, solder), KVP 28 (1⅛ in / 28 mm, solder) and KVP 35 (1⅜ in / 35 mm, solder). All five share a 0–5.5 bar regulating range with a factory setting of 2 bar. Flare connections exist only on KVP 12 and KVP 15 — everything larger is solder only.

Fit a KVP when a cold room over-cools on part load, an evaporator frosts up, product is drying out from too low an evaporating temperature, or two rooms at different temperatures are running off one compressor. Send us the duty and the line size and we will confirm the frame size.

Constant minimum evaporating pressure

maintained independent of system suction pressure

Multi-temperature evaporator staging

enables multiple evaporators at different temperatures on one compressor

Freezing and frosting protection

protects against product freezing and coil frosting

Effective pulsation damping

for long service life

Specifications

Function

Constant evaporating pressure regulation (opens on rising inlet pressure)

Sizing basis

Capacities based on liquid temp. ahead of expansion valve tl = 25 °C; regulator offset = 0.6 bar

Gas velocity limit

Inlet velocity should not exceed 40 m/s

Supplied across India from our Mumbai warehouse. Request a quotation for pricing and availability.